Measuring principle
- Current Single-phased current measurements by current shunt
- Voltage Single-phased voltage measurements by voltage divider
Nominal voltage Un
- 1×230 VAC -20 % – +15 %
- 2×230/400 VAC -20 % – +15 %
- 3×230/400 VAC -20 % – +15 %
Current : Itr – Ib (Imax) 0.25-5(100)A 35 mm²
Accuracy class MID: Class B
IEC: Class 0.5
Nominal frequency: fn 50 Hz ± 5 % or 60 Hz ± 5 %
Phase displacement: Unlimited
Operating temperature: -40 °C – +70 °C
Storage temperature: -40 °C – +85 °C
Protection class: IP54
Protection class II
Relative humidity
- < 75 % year’s average at 21 °C
- < 95 % less than 30 days/year, at 25 °C
Weight: 1300 g with no breaker
Application area Indoors or outdoors in suitable meter cabinet
Internal consumption.
Maximum power consumption of the current circuits with basic current: 0.01 VA 0,01 VA.
Maximum power consumption of the voltage circuits: 0.4 VA 0.1 W
Materials: Glass reinforced polycarbonate.
Data storage: EEPROM, > 10 years without voltage
Display:
- LCD, 7 mm digit height (value field)
- LCD, 5 mm digit height (identification readings)
- LCD, 3 mm digit height (voltage and tariff readings)
Meter constant: 10000 imp/kWh
S0 pulse diode: 10000 imp/kWh, kvarh
Pulse time: 30 ms ± 10 %
S0 pulse output: 1000 imp/kWh
Pulse time: 30 ms ± 10 %
Short circuit protection level: 4500 A
Real Time Clock (RTC) Accuracy: Typically 5 ppm at 23 °C
Backup Battery life > 10 years at normal operation
Supercap life > 10 years at normal operation
Supercap operating time 7 days fully charged